Looking for prices?
Sign in Become a Customer


3305548

Rittal TopTherm Blue e 3-Phase Cooling Unit, 400/460 VAC, 11.3/12.2 A, 540 cu-m/hr Internal, 950 cu-m/hr External Flow Rate, NEMA 1/2/3/3R/4/12/13/IP65/IP66 Enclosure, 5800 Btu


3305548

Rittal Cooling Unit, 3-Phase, Series: TopTherm Blue e, 400/460 VAC, 11.3/12.2 A, 0.65/0.78/0.82/0.96 kW Power, 50/60 Hz Frequency, 5800 Btu Capacity, NEMA 1/2/3/3R/4/12/13/IP65/IP66 Enclosure, 540 cu-m/hr Internal, 950 cu-m/hr External Flow Rate, 50 to 122 deg F, Wall Mounting, Carbon Steel, Light Gray, 1020 mm H x 405 mm W x 358 mm D Dimensions

Description
Energy-efficient Blue e wall-mounted cooling units with e-Comfort controller, RiNano coating on the condenser and electrical condensate evaporation integrated as standard, protection class UL Type 3R/4, 12.
Benefits
Suitable for outdoor installation Blue e technology. May be linked to the IoT interface via the Blue e IoT adaptor
Material
Carbon Steel
Colour
Light Gray
IP Rating
External Circuit: IP34, Internal Circuit: IP56
NEMA and UL Type Rating
UL Type 3R/4/12 with standard filter
Supply Includes
Nano-coated condenser wired ready for connection (plug-in terminal strip), drilling template fasteners, integral electric condensate evaporation
Note
Compressor cooling mode from 10 deg C ambient temperature. Only the internal fan is active in the temperature range -20 to 10 deg C
Variant
Wall-Mounted
Total Cooling Output to DIN EN 14511
L 35 L 35 @ 50 Hz: 1.49 kW L 35 L 35 @ 60 Hz: 1.7 kW L 35 L 50 @ 50 Hz: 1.04 kW L 35 L 50 @ 60 Hz: 1.17 kW
Air Throughput (Unimpeded Air Flow)
External circuit: 950 m sq/h Internal circuit: 540 m sq/h
Rated Operating Voltage
400V, 3~, 50 Hz, 460V, 3~, 60 Hz
Dimensions
40 in H x 16 in W x 14 in D
Temperature Control
e-Comfort Controller (factory setting 35 deg C)
Installation Depth
16 in
Temperature Range
Storage Temperature: -40 to 70 deg C, Operating Temperature: -20 to 50 deg C, Setting Range: 20 to 50 deg C
Refrigerant/Cooling Medium
500g of R134A
Rated Power Pel
L 35 L 35 at 50 Hz: 0.65 kW L 35 L 35 at 60 Hz: 0.82 kW L 35 L 50 at 50 Hz: 0.78 kW L 35 L 50 at 60 Hz: 0.96 kW
Maximum Rated Current
2.5 A at 50 Hz, 2.8 A at 60 Hz
Start-up Current (Max.)
12.2 A at 50 Hz, 11.3 A at 60 Hz
Pre-Fuse
Motor Circuit-Breaker: 6.3/10 A
Packaging Unit
1 pc
Gross Weight
52 kg
Add to Cart